Shanghai Huikong Energy Sources Consultation Co.,Ltd
|
Place of Origin: | Shanghai, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Item name | Sensing element | Curve | Compatible with |
N18 | Thermistor 1.8k at 25 °C | Curve 5 | TAC, CSI |
N3 | Thermistor 3k at 25 °C | Curve 6 | Alerton |
N10 | Thermistor 10k at 25 °C | Curve 24 | Hysine, Alerton,ALC, Delta,Trane, CSI |
N11 | Thermistor 10k at 25 °C | Curve 7 | Andover, Invensys, Carrier, KMC |
N20 | Thermistor 20k at 25 °C | Curve 20 | Honeywell |
N100 | Thermistor 100k at 25 °C | Curve 9 | Siemens SBT |
Tp1 | PT100 | 0.3851ohm/K | Honeywell |
Tp2 | PT1000 | 3.851ohm/K | Johnson Control |
TK5 | NI1000 | 5000ppm/k | Siemens SBT |
Sensing Element | Thermistor: Range Accuracy | NTC -30----70°C ±0.5k |
Platinum-Film: Range Accuracy | PT, 0.3851ohm/k -30----70°C ±0.3k | |
Nickel Thin Layer Range Accuracy | NI, 5000 ppm/k -30----70°C ±1k | |
Connection | Connection Terminals | 2.5 mm2 |
Environment | Operation Climatic Conditions Temperature Humidity | To IEC 721-3-3 class 3 K5 -4070°C <95% r.h. |
Transport & Storage Climatic Conditions Temperature Humidity Mechanical Conditions | To IEC 721-3-2 and IEC 721-3-1 class 3 K3 and class 1 K3 -4080°C <95% r.h. class 2M2 | |
Standards | conform according to EMC Standard 89/336/EEC EMEI Standard 73/23/EEC | EN 61 000-6-1/ EN 61 000-6-3 |
Automatic electrical controls for household and similar use Special requirement on temperature dependent controls | EN 60 730 1 EN 60 730 2 - 9 | |
Pollution Class | Normal acc. To EN 60 730,RoHS compliant | |
Degree of Protection | IP56 to EN 60 529 | |
Safety Class | III (IEC 60536) | |
Housing Materials | Cover & Mounting Plate | Fire proof ABS plastic |
General | Dimensions [mm] | Cover: 42 x 112 x 88 (H x W x D) |
Weight (including package) | 135g |