Features
· Thermistor,PT or NI sensing elements to fit your system
· Simple and secure installation
· Wide range of temperature probes
· Compact size and modern design
Applications
· On return air ducts to measure heating/cooling return air
· On supply air ducts to measure heating/cooling supply air
· In heat exchangers and air handling units to control heating/cooling coils for temperature and humidity control
· As frost protection sensor
Temperature Sensor
The sensor measures the temperature by use of a NTC, PT or NI sensing element. The sensing element is either a glass packed thermistor with a negative temperature coefficient or a platinum film sensor or a thin nickel layer on a ceramic substrate. Its resistance changes according to the temperature. The change follows a specified curve. Below is a list of available sensor elements, curves and accuracies:
Item name | Sensing element | Curve | Compatible with |
N18 | Thermistor 1.8k at 25 °C | Curve 5 | TAC, CSI |
N3 | Thermistor 3k at 25 °C | Curve 6 | Alerton |
N10 | Thermistor 10k at 25 °C | Curve 24 | Hysine, Alerton,ALC, Delta,Trane, CSI |
N11 | Thermistor 10k at 25 °C | Curve 7 | Andover, Invensys, Carrier, KMC |
N20 | Thermistor 20k at 25 °C | Curve 20 | Honeywell |
N100 | Thermistor 100k at 25 °C | Curve 9 | Siemens SBT |
Tp1 | PT100 | 0.3851ohm/K | Honeywell |
Tp2 | PT1000 | 3.851ohm/K | Johnson Control |
TK5 | NI1000 | 5000ppm/k | Siemens SBT |
Ordering
Ordering number:TS-XX-D-YY
XX indicates the sensor element optional,see table above.
YY indicates the probe length. Standard probe length is 20 cm.
For example:TS-N10-D-20
-N10 indicates the sensor element is Thermistor 10k .
-20 indicates the probe length is 20 cm.
Duct probes should be installed directly on the duct, in an area where the air stream is well mixed:
· Locate a supply air sensor two or three meters down stream from the nearest fan and coil.
· Mount the return air sensor close to the air inlet but downstream from a return fan if one is present.
· To install the sensor, assemble base plate and probe, then drill a 8 mm hole and two 3 mm holes on a diameter of 25 mm in the duct.
· Use two self-tapping sheet metal screws to tighten the mounting circuit in the cover.
· Connect the wires according to the wiring diagram to the measuring circuit in the cover:
o The Thermistors require two conductors; normally 18ga unshielded twisted pair.
o The PT100, PT1000 and NI1000 sensors come with each two terminal connectors in order to connect up to four conductors for compensating conductor resistance.
· Assemble the cover with the mounting plate.
· Insert the assembled probe through the center opening of the mounting plate into the air stream.
· Tighten the horizontal screw on the mounting plate to fix the probe to the duct.
Technical Specification
Sensing Probe | Thermistor: Range Accuracy | NTC -30----70°C ±0.5k |
Platinum-Film: Range Accuracy | PT, 0.3851ohm/k -30----70°C ±0.3k |
Nickel Thin Layer Range Accuracy | NI, 5000 ppm/k -30----70°C ±1k |
Connection | Connection Terminals | 2.5 mm2 |
Environment | Operation Climatic Conditions Temperature Humidity | To IEC 721-3-3 class 3 K5 -4070°C <95% r.h. |
Transport & Storage Climatic Conditions Temperature Humidity Mechanical Conditions | To IEC 721-3-2 and IEC 721-3-1 class 3 K3 and class 1 K3 -4080°C <95% r.h. class 2M2 |
Standards | conform according to EMC Standard 89/336/EEC EMEI Standard 73/23/EEC | EN 61 000-6-1/ EN 61 000-6-3
|
Automatic electrical controls for household and similar use Special requirement on temperature dependent controls | EN 60 730 1 EN 60 730 2 - 9 |
Pollution Class | Normal acc. To EN 60 730,RoHS compliant |
Degree of Protection | IP56 to EN 60 529 |
Safety Class | III (IEC 60536) |
Housing Materials | Cover & Mounting Plate Probe | Fire proof ABS plastic Stainless Steel |
General | Dimensions [mm] | Cover: 42 x 112 x 88 (H x W x D) Probe: ø 6 x 200 (Diameter x L) |
Weight (including package) | 135g |